Product Overview
| Suitable Applications | Horizontal and building backbone cable; Support current and future Category 6 and 5e applications, such as: 1000Base – T (Gigabit Ethernet), 100 Base – T, 10 Base – T, FDDI, ATM | 
|---|
Physical Characteristics (Overall)
CONDUCTOR
| Element | AWG | Stranding | Material | No. of Pairs | 
|---|---|---|---|---|
| Individual pair | 23 | Solid | BC – Bare Copper | 4 | 
| Conductor Count | 8 | 
|---|---|
| Total Number of Pairs | 4 | 
INSULATION
| Element | Type | Material | Nominal Diameter | 
|---|---|---|---|
| Individual pair | Dielectric | PE – Polyethylene | 1.35 mm | 
| Bonded-Pair | Yes | 
|---|
COLOR CHART
| Number | Color | 
|---|---|
| Pair 1 | White/Blue & Blue | 
| Pair 2 | White/Green & Green | 
| Pair 3 | White/Orange & Orange | 
| Pair 4 | White/Brown & Brown | 
CABLING
| Description | Filler | 
|---|---|
| 4 pairs twisted together covered with a polyester foil | Cross Web of Polyolefin | 
OUTER SHIELD MATERIAL
| Type | Material | Coverage [%] | Drainwire Material | Drainwire AWG | Drainwire Construction n x D | Drainwire Position | 
|---|---|---|---|---|---|---|
| Tape | Bi-Laminate (Alum+Poly) | 100% | TC – Tinned Copper | 26 | Solid | Over foil | 
| Table Notes | Aluminum facing outside in contact with drain wire | 
|---|
OUTER JACKET MATERIAL
| Material | Nominal Diameter | Diameter +/- Tolerance | 
|---|---|---|
| LSZH – Low Smoke Zero Halogen (Flame Retardant) | 7.3 mm | 0.3 mm | 
Construction and Dimensions
| Min Elongation at Breakof Conductors | 10 % | 
|---|---|
| Min Elongation at Breakof Insulation | 100 % | 
| Min Elongation at Breakof Jacket | 100 % | 
|---|---|
| Min Tensile Strength of Jacket | 9 MPa | 
Electrical Characteristics
CONDUCTOR DCR
| Max. Conductor DCR | Max DCR Unbalanced Between Pairs [%] | Max. DCR Unbalanced Within Pair [%] | 
|---|---|---|
| 95 Ohm/km | 4 % | 2 % | 
CAPACITANCE
| Max. Capacitance Unbalance | Max. Mutual Capacitance | 
|---|---|
| 1,600 pF/km | 56 pF/m | 
IMPEDANCE
| Nominal Characteristic Impedance | 
|---|
| 100 Ohm | 
DELAY
| Max. Delay Skew | Nominal Velocity of Propagation (VP) [%] | 
|---|---|
| 40 ns/100m | 67% | 
| Table Notes | Limits below 4 MHz are for information only. Reference standard: IEC 61156-5 | 
|---|---|
| General Electrical Parameters Notes | Reference standard: ISO/IEC 61156-5 | 
| Coupling Attenuation Class | Type II | 
|---|---|
| Segregation class according EN50174-2 | c | 
TRANSFER IMPEDANCE
| Frequency [MHz] | Transfer Impedance | 
|---|---|
| 1 Mhz | Max. 50 mOhm/m | 
| 10 Mhz | Max. 100 mOhm/m | 
| 30 Mhz | Max. 200 mOhm/m | 
| 100 Mhz | Max. 1000 mOhm/m | 
| Transfer Impedance Class | Grade 2 | 
|---|
CURRENT
| Max. Recommended Current [A] | 
|---|
| 1.5 Amps per Conductor | 
VOLTAGE
| Voltage Rating [V] | 
|---|
| 72 V | 
Temperature Range
| Installation Temp Range | 0°C To +50°C | 
|---|---|
| Operating Temp Range | -30°C To +60°C | 
Mechanical Characteristics
| Bulk Cable Weight | 50 kg/km | 
|---|---|
| Max. Pull Tension | 80 N | 
| Min. Bend Radius During Installation | 58 mm | 
| Min Bend Radius During Operation | 29 mm | 
Standards
| ISO/IEC Compliance | ISO/IEC 11801-1 | 
|---|---|
| CPR Euroclass | Dca-s2,d1,a1 | 
| CENELEC Compliance | EN 50173-1 | 
| Data Category | Category 6 | 
| ANSI Compliance | ANSI/TIA 568.2-D (2018) | 
| IEEE Compliance | PoE: IEEE 802.3bt Type 1, Type 2, Type 3, Type 4 | 
Applicable Environmental and Other Programs
| Environmental Space | Indoor – Euroclass Dca | 
|---|---|
| EU RoHS Compliance Date (yyyy-mm-dd) | 2005-01-01 | 
Flammability, LS0H, Toxicity Testing
| IEC Flammability | IEC 60332-1-2 | 
|---|---|
| Burning Load | 745 kJ/m | 
| IEC 60754-1 – Halogen Amount | Zero | 
| IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity | 2.5 µS/mm | 
| IEC 60754-2 – Halogen Acid Gas Amount – Min. pH | 4.3 | 
| IEC 61034-2 – Smoke Density Min. Transmittance | 60% | 
Product Notes
| Notes | Electrical values are expected performance based on cable testing and representative performance within a typical Belden system. | 
|---|
History
| Update and Revision | Revision Number: 0.349 Revision Date: 08-27-2021 | 
|---|
Part Numbers
| Item # | Color | Put-Up Type | Length | EAN | 
|---|---|---|---|---|
| 7860ENH.03500 | Black | Reel | 500 m | 8719605016515 | 
| 7860ENH.K1305 | Blue | Reel | 305 m | 8719605167859 | 
| 7860ENH.01500 | Blue | Reel | 500 m | 8719605016485 | 
| 7860ENH.011000 | Blue | Reel | 1,000 m | 8719605016478 | 
	