Specifications
|
||
---|---|---|
Model | Salicru 662AG000011 Line Interactive 2000VA UPS | |
Technology | Line-interactive | |
Format | Convertible tower/rack (2U) | |
INPUT | ||
Rated Voltage | 208 V / 220 V / 230 V / 240 V | |
Voltage Range (100% load) | 170 V ÷ 280 V | |
Stabilizer | AVR (Buck & Boost) | |
Rated Frequency | 50 / 60 Hz (auto-detection) | |
Frequency Range | ±5 Hz | |
Auto Detection of Frequency | Yes | |
Protection | Fuse (800/1100) or resettable thermal cutoff (1500/2000/3000) | |
OUTPUT | ||
Power Factor | 0.9 | |
Rated Voltage | 208 V / 220 V / 230 V / 240 V | |
Voltage Accuracy (Battery Mode) | ±1.5% | |
Power (VA/W) | 2000 VA / 1800 W | |
Total Harmonic Distortion (THDv) | < 2% (linear load) / < 5% (non-linear load) | |
Waveform (Battery Mode) | Pure sine wave | |
Frequency | 50 / 60 Hz (same as input) | |
Frequency Accuracy (Battery Mode) | ±0.1 Hz | |
Admissible Overloads in Battery Mode | < 120% off at 1 min / < 150% off at 10 s | |
Admissible Overloads in Line Mode | < 120% off at 5 min / < 150% off at 10 s / >150 %: 1 s | |
Socket Type | IEC | |
No. of Sockets | 8 | |
Programmable Sockets | Yes, for critical / non-critical loads (4/4) | |
BATTERY | ||
Battery Type | Pb-Ca sealed, AGM, maintenance-free | |
Charge Type | I/U (constant current/constant voltage) | |
Recharge Time | 4 hours to 90% | |
Battery Test | Automatic on every start + one time per week | |
CHARGER | ||
Temperature Voltage Compensation | Yes | |
COMMUNICATION | ||
Ports | RS-232 / USB-HID | |
Intelligent Slot | Slot for SNMP/potential-free contacts/ MODBUS | |
Monitoring Software | Compatible with Windows, Linux, and Mac | |
INDICATIONS | ||
Type | LCD + keypad | |
Display Values | Voltage, power and input/output frequency, battery voltage, % battery charge, % load, operating mode, fault, discharge time, mute | |
Operating Modes | Normal / Stabilisation (AVR) / Battery / Fault | |
Alarm | Output battery mode, polarity, low battery, charger failure, overload | |
Audible Alarm | Every 10 s for battery operation. Every 2 s for low battery / Polarity. Every 1 s for overcharge. Continuous for fault. | |
Failure Display | LCD | |
OTHER FUNCTIONS | ||
Cold Start | Yes | |
Emergency Stop (EPO) | Yes | |
ADSL/Fax/Modem Transient Protector | Yes | |
Green Function | Yes, automatic stop in battery mode with load <5% | |
Smart Fan Speed | Yes, smart control of fan speed | |
Site Wiring Fault | Yes, error detection of phase-neutral rotation and/or absence of earth | |
GENERAL | ||
Operating Temperature | 0ºC to +40ºC | |
Relative Humidity | Up to 95%, non-condensing | |
Maximum Operating Altitude | 2400 meters above sea level (power degradation up to 5,000 m) | |
Acoustic Noise at 1 Meter | < 45 dB | |
STANDARDS | ||
Safety | EN IEC 62040-1 | |
Electromagnetic Compatibility (EMC) | EN IEC 62040-2 (C2) | |
Operation | EN IEC 62040-3 | |
Corporate Certification | ISO 9001, ISO 14001, ISO 45001 | |
DIMENSIONS | ||
Depth (mm) | 510 mm | |
Width (mm) | 438 mm | |
Height (mm) | 88 mm | |
WEIGHT | ||
Weight (kg) | 21.5 kg | |
Warranty | 3 years on electronics, 2 years on battery replacement. |